Basic principles For testing partial functions of the control program (e.g. EtherCAT diagnosis) at an earlier time (before virtual commissioning), the control computer can also be used to simulate the EtherCAT, as long as the control computer has sufficient free network interfaces. Just like every EtherCAT master, every EtherCAT simulation device also requires its own network interface. Using a CX as controller If a CX is used as controller that is to be coupled with a simulation IPC, there may still be EtherCAT devices available depending on the cabling, which must not be taken into account.
The following figure shows, for example, the intelligent power supply unit of the CX and an EK1110 EtherCAT extension. Here in the Settings tab [ } 24] a manual device correction can be set, i.e. devices that should not be considered. If this setting is not set, this could result in the EtherCAT master not starting up or the working counter not being calculated correctly. Use of the port multiplier on the original project page: If a CU2508 port multiplier is used in the real-time configuration of the control computer, the outputs of the port multiplier can be connected to normal network ports on a simulation computer.
For these network ports, a corresponding number of EtherCAT simulation devices must be created on the simulation computer. TE1111 11 Version: 1.5.3