beckhoff TF4100 — 4.2.1.4.14 FB_CTRL_PTt

PLC API stParams consists of the following elements: TYPE ST_CTRL_PTn_PARAMS : STRUCT tCtrlCycleTime : TIME := T#0ms; tTaskCycleTime : TIME := T#0ms; fKp : FLOAT := 0; tT1 : TIME := T#0ms; END_STRUCT END_TYPE 4.2.1.4.14 FB_CTRL_PTt The function block provides an PTt transfer element in the functional diagram. Transfer function ( ) t T s p G s K e - = g This function block contains internally an array of 500 elements with which the input values can be delayed. When using the tCtrlCycleTime this results in a maximum delay of "500 * tCtrlCycleTime". If this maximum delay is insufficient, the sampling time is extended internally to make it possible to reach the requested dead time.

It should, however, be remembered that this process involves increasing the time between the discretization steps. If a new sampling time has been calculated, this is indicated by a TRUE on the bSampleRateChanged output. Inputs VAR_INPUT fIn : FLOAT; fManSyncValue : FLOAT; bSync : BOOL; eMode : E_CTRL_MODE; END_VAR TF4100 110 Version: 2.2.4 Name Type Description stParams ST CTRL PTn _ _ _ PARAMS Parameter structure of the PTn element Name Type Description tCtrlCycleTime TIME Cycle time with which the control loop is processed. This must be greater than or equal to the TaskCycleTime.

The function block uses this input value to calculate internally whether the state and the output values have to be updated in the current cycle. tTaskCycleTime TIME Cycle time with which the function block is called. If the function block is called in every cycle this corresponds to the task cycle time of the calling task. fKp FLOAT Controller amplification / transfer coefficient tT1 TIME Time constant T1