PLC API 4.2.1.5 Interpolation 4.2.1.5.1 FB_CTRL_LIN_INTERPOLATION This function block performs linear interpolation to obtain values on the basis of a sampling points table. Behavior of the output TF4100 118 Version: 2.2.4 Name Type Description tCtrlCycleTime TIME Cycle time with which the control loop is processed. This must be greater than or equal to the TaskCycleTime. The function block uses this input value to calculate internally whether the state and the output values have to be updated in the current cycle. tTaskCycleTime TIME Cycle time with which the function block is called. If the function block is called in every cycle this corresponds to the task cycle time of the calling task.
fDampingCo efficient FLOAT The parameter corresponds to k in the transfer function. damping fIn fOut arrTable[1,1] := 10; arrTable[1,2] := 7; arrTable[2,1] := 15; arrTable[2,2] := 10; arrTable[3,1] := 21; arrTable[3,2] := 9; arrTable[4,1] := 22; arrTable[4,2] := 2; arrTable[5,1] := 30; arrTable[5,2] := 3; arrTable[6,1] := 40; arrTable[6,2] := 6;