beckhoff TF4100 — 4.2.1.7.3 FB_CTRL_MULTIPLE_PWM_OUT

PLC API TYPE ST_CTRL_LIMITER_PARAMS: STRUCT tCtrlCycleTime : TIME := T#0ms; tTaskCycleTime : TIME := T#0ms; fMinOutput : FLOAT; fMaxOutput : FLOAT; END_STRUCT END_TYPE 4.2.1.7.3 FB_CTRL_MULTIPLE_PWM_OUT This function block creates PWM modulated output signals from a number of input signals in such a way that the temporal relationships between the output signals are arranged so that as few outputs as possible are switched on at any one time. This temporal arrangement reduces the maximum power necessary required for the actuators. Both the minimum switch-on time and the minimum switch-off time can be parameterized, in addition to the mark-to-space ratio, in this extended function block.

TF4100 135 Version: 2.2.4 Name Type Description tCtrlCycleTime TIME Cycle time with which the control loop is processed. This must be greater than or equal to the TaskCycleTime. The function block uses this input value to calculate internally whether the state and the output values have to be updated in the current cycle. tTaskCycleTime TIME Cycle time with which the function block is called. If the function block is called in every cycle this corresponds to the task cycle time of the calling task. fMinOutput FLOAT Lower limit to which the output is restricted. fMaxOutput FLOAT Upper limit to which the output is restricted.