PLC API 4.2.1.7.8 FB_CTRL_SPLITRANGE This function block divides an input signal into positive and negative components. The parameters bDisablePosOut and bDisableNegOut can be used to deactivate the positive or negative output → heating mode only during the winter, cooling mode only during the summer. The bInvertNegOutput parameter allows the negative output to be inverted. TF4100 148 Version: 2.2.4 Name Type Description tCtrlCycleTime TIME Cycle time with which the control loop is processed. This must be greater than or equal to the TaskCycleTime. The function block uses this input value to calculate internally whether the state and the output values have to be updated in the current cycle.
tTaskCycleTime TIME Cycle time with which the function block is called. If the function block is called in every cycle this corresponds to the task cycle time of the calling task. tMovingTime TIME The time required to move the actuator from one stop to the other. tSignalExtension TIME Signal extension by which each output pulse is extended in order to compensate for the dead time. tAdditionalMoveT imeAtLimits TIME Supplementary signal extension, output to reliably reach the limits when the actuator is to be driven to +/-100%. Only effective if bMoveOnLimitSwitch is FALSE.
tMinWaitTime Between DirectionChange TIME Minimum waiting time between positive and negative output pulses tMinimumPulse Time TIME Minimum length of an output pulse bMoveOnLimit Switch BOOL If TRUE, then when the control value is either fCtrlOutMin or fCtrlOutMax a signal will continue to be output until the corresponding limit switch is reached. bStopAdditionalM oveTimeIf InputValueIs Changed BOOL If this flag is TRUE, movement of the valve to the end position, which is triggered by "Additional Moving Time At Limits", is stopped, if an input value is specified that does not match the end position.
If this flag is FALSE and the input value matches an end position, the valve always safely moves to the end position first, before it can move to a different valve position. fCtrlOutMax FLOAT Control value for which the valve will be driven to 100%. fCtrlOutMin FLOAT Control value for which the valve will be driven to 0%.