PLC API It can clearly be seen in the following scope trace that the original target position of 1000 mm is exceeded, the reason being that the new parameter set had a reduced deceleration. 4.2.1.8.2 FB_CTRL_FLOW_TEMP_SETPOINT_GEN This function block enables specification of a flow temperature depending on the outdoor temperature. Description The setpoint for the flow temperature ( fOut ) is determined from the ambient temperature ( fAmbientTemperature ). A straight line that can be moved via an offset ( fOffsetTemperature ) is used for this purpose. The slope is determined based on the specified ambient and flow temperature corners.
A flag ( bLimitFlowTemp ) is used to specify whether or not the flow temperature is restricted to its limit values. The offset temperature can be used to realize a night setback or pre-control. TF4100 162 Version: 2.2.4