PLC API 4.2.1.8.6 FB_CTRL_SIGNAL_GENERATOR The function block provides a signal generator offering triangular, sine and sawtooth signal forms. TF4100 171 Version: 2.2.4 Name Type Description tCtrlCycleTime TIME Cycle time with which the control loop is processed. This must be greater than or equal to the TaskCycleTime. The function block uses this input value to calculate internally whether the state and the output values have to be updated in the current cycle. Indent: -103; margin-left: 108"> tTaskCycleTime TIME Cycle time with which the function block is called. If the function block is called in every cycle this corresponds to the task cycle time of the calling task.
pDataTable ADR _ POINTER TO INTERPOLATION _ TABLE ELEMEN _ T Address of the data array nDataTable SIZ _ EOF UINT Size of the data array nDataTable Num _ berOfRows UINT Number of rows in the data array fVeloPos FLOAT Velocity in unit/s, with which the output is changed from a lower value to a higher one. fVeloNeg FLOAT Velocity in unit/s, with which the output is changed from a higher value to a lower one. bDisableRampin g BOOL A continuous output value is not calculated if this parameter is TRUE. There is a step change between the output values.