PLC API The outputs of the function blocks eState This output indicates the current internal state of the function block. bError An error in the function block is indicated by a TRUE at this boolean output. eErrorId The error number [ } 173] is provided at this output if the bError output is TRUE. Using the global base time In order to be able to use the function blocks of a PLC task with a cycle time of less than 1ms, it is possible to interpret the specified cycle times as ticks of a base time. In this special parameterization, the time unit of 1ms is interpreted as 1 tick. This approach is equivalent to setting a PLC cycle time of less than 1ms in the TwinCAT System Manager.
The switchover and declaration of the base time is done with the global structure stCtrl_GLOBAL_CycleTimeInterpretation for all function blocks of the toolbox. VAR_GLOBAL stCtrl_GLOBAL_CycleTimeInterpretation : ST_CTRL_CYCLE_TIME_INTERPRETATION; END_VAR TYPE ST_CTRL_CYCLE_TIME_INTERPRETATION : STRUCT bInterpretCycleTimeAsTicks : BOOL; (* e.g. 2ms -> 2ticks *) fBaseTime : FLOAT; (* Base time in seconds, e.g. 200µs -> 200E-6s *) END_STRUCT END_TYPE TF4100 19 Version: 2.2.4 Task: Configuration Parameter: tTaskCycleTime Parameter: tCtrlCycleTime Action T#10ms T#10ms T#10ms The control loop is processed using a 10 ms sampling time.
T#10ms T#10ms T#50ms The control loop is processed using a 50 ms sampling time. T#100ms T#100ms T#100ms The control loop is processed using a 100 ms sampling time. T#100ms T#100ms T#50ms ERROR, execution is not possible! T#100ms T#50ms T#50ms ERROR, although the function block has been executed, incorrect output values have been calculated! eCTRL STATE IDLE _ _ The function block has successfully been reset, and is now waiting for selection of the operation mode. eCTRL STATE PASSIVE _ _ The function block is in the passive state in which no calculations are carried out. eCTRL STATE ACTIVE _ _ The function block is in the active state, which is the normal operating state.
eCTRL STATE RESET _ _ A reset request is being processed, but the reset has not yet been completed. eCTRL STATE MANUAL _ _ The function block is in the manual state, and the output value can be manually specified at the appropriate input. eCTRL STATE ... _ _ If there are any other internal states, they are described together with the corresponding function blocks. eCTRL STATE ERROR _ _ An error has occurred; the function block is not executed when in this state. See eErrorId for further information.