PLC API Outputs VAR_OUTPUT fOut : FLOAT; eState : E_CTRL_STATE; eErrorId : E_CTRL_ERRORCODES; bError : BOOL; END_VAR Inputs/ outputs VAR_IN_OUT stParams : ST_CTRL_D_PARAMS; END_VAR stParams consists of the following elements: TYPE ST_CTRL_D_PARAMS: STRUCT tCtrlCycleTime : TIME := T#0ms; tTaskCycleTime : TIME := T#0ms; tTv : TIME := T#0ms; tTd : TIME := T#0ms; fOutMaxLimit : FLOAT := 1E38; fOutMinLimit : FLOAT := -1E38; END_STRUCT END_TYPE TF4100 34 Version: 2.2.4 Name Type Description fIn FLOAT Input of the D element fManSyncValue FLOAT Input to which the D-element can be synchronized, or whose value is present at the output in Manual Mode.
bSync BOOL A rising edge at this input sets the D-element to the value "fManSyncValue". eMode E CTRL MODE _ _ Input that specifies the operation mode [} 173] of the function block. Name Type Description fOut FLOAT Output of the D element eState E CTRL STATE _ _ State of the function block eErrorId E CTRL ERROR _ _ CODES Supplies the error number [} 173] when the output bError is set. bError BOOL Becomes TRUE, as soon as an error occurs. Name Type Description stParams ST CTRL D _ _ _ PARAMS Parameter structure of the D-element Name Type Description tCtrlCycleTime TIME Cycle time with which the control loop is processed. This must be greater than or equal to the TaskCycleTime.
The function block uses this input value to calculate internally whether the state and the output values have to be updated in the current cycle. tTaskCycleTime TIME Cycle time with which the function block is called. If the function block is called in every cycle this corresponds to the task cycle time of the calling task. tTv TIME Differentiation time constant tTd TIME Damping time constant fOutMaxLimit FLOAT Upper limit to which the output of the D-element is restricted. fOutMinLimit FLOAT Lower limit to which the output of the D-element is restricted.