beckhoff TF4100 — 4.2.1.3.1 FB_CTRL_2POINT

PLC API Outputs VAR_OUTPUT bOut : BOOL; eState : E_CTRL_STATE; eErrorId : E_CTRL_ERRORCODES; bError : BOOL; END_VAR VAR_IN_OUT stParams : ST_CTRL_2POINT_PARAMS; END_VAR Input/ outputs stParams consists of the following elements: TYPE ST_CTRL_2POINT_PARAMS : STRUCT tCtrlCycleTime : TIME := T#0ms; tTaskCycleTime : TIME := T#0ms; fHysteresisRange : FLOAT; END_STRUCT END_TYPE TF4100 42 Version: 2.2.4 Name Type Description fSetpointValue FLOAT Setpoint of the controlled variable fActualValue FLOAT Actual value of the controlled variable bManSyncValue BOOL Input through which the 2-point element can be set to one of the two junctions.

bSync BOOL A rising edge at this input sets the 2-point element to the value "bManSyncValue". eMode E CTRL MODE _ _ Input that specifies the operation mode [} 173] of the function block. Name Type Description bOut BOOL Output of the 2-point element eState E CTRL STATE _ _ State of the function block eErrorId E CTRL ERROR _ _ CODES Supplies the error number [} 173] when the output bError is set. bError BOOL Becomes TRUE, as soon as an error occurs. Name Type Description stParams ST CTRL _ _ 2POINT _ PARAMS Parameter structure of the 2-point element Name Type Description tCtrlCycleTime TIME Cycle time with which the control loop is processed.

This must be greater than or equal to the TaskCycleTime. The function block uses this input value to calculate internally whether the state and the output values have to be updated in the current cycle. tTaskCycle Time TIME Cycle time with which the function block is called. If the function block is called in every cycle this corresponds to the task cycle time of the calling task. fHysteresis Range FLOAT Hysteresis range, see diagram above.