PLC API 4.2.1.3.3 FB_CTRL_3POINT The function block provides a 3-point transfer element in the functional diagram. Behavior of the output TF4100 45 Version: 2.2.4 Name Type Description tCtrlCycleTime TIME Cycle time with which the control loop is processed. This must be greater than or equal to the TaskCycleTime. The function block uses this input value to calculate internally whether the state and the output values have to be updated in the current cycle. tTaskCycleTime TIME Cycle time with which the function block is called. If the function block is called in every cycle this corresponds to the task cycle time of the calling task.
tPWMPeriod TIME Period of the PWM signal fOkRange FLOAT The range of "fE" over which the mark-to-space ratio will not be modified. fForceRange FLOAT If "fE" exceeds this range, the output is permanently set to TRUE. fStepSize FLOAT Value by which the mark-to-space ratio is varied each time it is adapted. [0% ... 100%] fMinLimit FLOAT Maximum mark-to-space ratio in percent [0% ... 100%] fMaxLimit FLOAT Minimum mark-to-space ratio in percent [0% ... 100%] tWaitTime TIME Waiting time between individual modifications of the mark-to-space ratio