beckhoff TF4100 — 4.2.1.3.4 FB_CTRL_3POINT_EXT

PLC API fNegOutOff : FLOAT; END_STRUCT END_TYPE 4.2.1.3.4 FB_CTRL_3POINT_EXT The function block provides an extended 3-point element in the functional diagram. Behavior of the output fIn := fSetpointValue - fActualValue; TF4100 47 Version: 2.2.4 Name Type Description tCtrlCycleTime TIME Cycle time with which the control loop is processed. This must be greater than or equal to the TaskCycleTime. The function block uses this input value to calculate internally whether the state and the output values have to be updated in the current cycle. tTaskCycle Time TIME Cycle time with which the function block is called.

If the function block is called in every cycle this corresponds to the task cycle time of the calling task. fPosOutOn FLOAT Control deviation that will result in bPosOut = FALSE being switched to bPosOut = TRUE (bNegOut = FALSE). fPosOutOff FLOAT Control deviation that will result in bPosOut = TRUE being switched to bPosOut = FALSE (bNegOut = FALSE). fNegOutOn FLOAT Control deviation that will result in bNegOut = FALSE being switched to bNegOut = TRUE (bPosOut = FALSE). fNegOutOff FLOAT Control deviation that will result in bNegOut = TRUE being switched to bNegOut = FALSE (bPosOut = FALSE).