beckhoff TF4100 — 4.2.1.3.6 FB_CTRL_PARAMETER_SWITCH

PLC API 4.2.1.3.6 FB_CTRL_PARAMETER_SWITCH This function block can be used to switch the parameter set used by FB_CTRL_PID_SPLITRANGE . Behavior of the output TF4100 52 Version: 2.2.4 Name Type Description tCtrlCycleTime TIME Cycle time with which the control loop is processed. This must be greater than or equal to the TaskCycleTime. The function block uses this input value to calculate internally whether the state and the output values have to be updated in the current cycle. tTaskCycle Time TIME Cycle time with which the function block is called. If the function block is called in every cycle this corresponds to the task cycle time of the calling task.

pDataTable _ ADR POINTER TO nPOINT CTRL _ _ TABLE _ ELEMENT Address of the data table nDataTable _ SIZEOF UINT Size of the data table in bytes nDataTable _ NumberOf Rows UINT Number of rows in the data table fHysteresis Range FLOAT Hysteresis range, see diagram above. The hysteresis range functions as described for FB CTRL 2POINT [} 41]. _ _