PLC API Functional diagram for the cascaded transfer element Inputs VAR_INPUT fSetpointValue : FLOAT; fActualValueOuterLoop : FLOAT; fActualValueInnerLoop : FLOAT; fPreControl : FLOAT; fManSyncValueInnerLoop : FLOAT; bSyncInnerLoop : BOOL; eModeInnerLoop : E_CTRL_MODE; bHoldInnerLoop : BOOL; fManSyncValueOuterLoop : FLOAT; bSyncOuterLoop : BOOL; eModeOuterLoop : E_CTRL_MODE; bHoldOuterLoop : BOOL; END_VAR TF4100 58 Version: 2.2.4 Name Type Description fSetpointValue FLOAT Setpoint of the controlled variable fActualValueOute rLoop FLOAT The actual value of the controlled variable that is fed back to the PI controller of the outer control loop.
fActualValueInne rLoop FLOAT The actual value of the controlled variable that is fed back to the PID controller of the inner control loop. fPreControl FLOAT Pre-control that is connected behind the PI controller. fManSyncValueIn nerLoop FLOAT Input, to whose value it is possible to set the internal state of the PID- element (the inner control loop). bSyncInnerLoop BOOL A rising edge at this input sets the PID-element (the inner control loop) to the value "fManSyncValueInnerLoop". eModeInnerLoop E CTRL MODE _ _ Input that specifies the operation mode [} 173] of the PID-element (the inner control loop).
bHoldInnerLoop BOOL A TRUE at this input holds the internal state of the PID-element (the inner control loop) constant at the current value. fManSyncValueO uterLoop FLOAT Input, to whose value it is possible to set the internal state of the PI element (the outer control loop). bSyncOuterLoop BOOL A rising edge at this input sets the PI element (the outer control loop) to the value "fManSyncValueOuterLoop". eModeOuterLoop E CTRL MODE _ _ Input that specifies the operation mode [} 173] of the PI element (the outer control loop). bHoldOuterLoop BOOL A TRUE at this input holds the internal state of the PI element (the outer control loop) constant at the current value.