PLC API Functional diagram The standard functional diagram of a PID controller in additive form has been expanded by the two active boolean Inputs bPInTheFeedbackPath and bDInTheFeedbackPath (which act as "switches"), so that a modified functional diagram can be activated. Control background: due to the differential component of the control algorithm, large control values are generated at setpoint step-changes, which cause a strain on the control elements and may cause the control system to oscillate. A control algorithm whose differential component is only applied to the control value ( bDInTheFeedbackPath := TRUE ) avoids this problem.
The bPInTheFeedbackPath and bDInTheFeedbackPath Inputs permit the closed control loop to implement the following transfer functions: with: T s G s K T s T s ж ц = + з ч + и ш v DI p 1 ( ) 1 n d TF4100 61 Version: 2.2.4 bPInTheFeedbackPath bDInTheFeedbackPath G(s) false false G ( s)×G ( s) G ( s)= PID S 1+G ( s)×G ( s) PID S true false G ( s)×G ( s) G ( s)= DI S 1+G ( s)×G ( s) PID S false true G ( s)×G ( s) G ( s)= PI S 1+G ( s)×G ( s) PID S true true G ( s)×G ( s) G ( s)= I S 1+G ( s)×G ( s) PID S