PLC API ARW VAR_INPUT fSetpointValue : FLOAT; fActualValue : FLOAT; fManSyncValue : FLOAT; bSync : BOOL; eMode : E_CTRL_MODE; bHold : BOOL; END_VAR Inputs Outputs VAR_OUTPUT fOut : FLOAT; bARWactive : BOOL; eState : E_CTRL_STATE; eErrorId : E_CTRL_ERRORCODES; bError : BOOL; END_VAR TF4100 63 Version: 2.2.4 Name Type Description fSetpointValue FLOAT Setpoint of the controlled variable fActualValue FLOAT Actual value of the controlled variable fManSyncValue FLOAT Input, to whose value it is possible to set the internal state of the PID- element. bSync BOOL A rising edge at this input sets the PID-element to the value "fManSyncValue".
eMode E CTRL MODE _ _ Input that specifies the operation mode [} 173] of the function block. bHold BOOL A TRUE at this input will hold the internal state (and therefore also the output) constant at its current value, independently of the control deviation.