PLC API 4.2.1.3.10 FB_CTRL_PID_EXT_SPLITRANGE The function block provides an extended PID transfer element in the functional diagram. With this controller it is possible to switch between two different parameter sets while the regulation is active. The functionalities of the inner and outer windows and of the input and output dead bands are available in addition. Description This function block is an extension of FB_CTRL_PID_EXT , which means that the controller can be used to control systems with two controlled devices for which the transfer behavior are different. A system with one actuator for heating and another actuator for cooling would be a typical application.
To optimize the regulation of such an arrangement, it is possible to switch between two PID parameter sets. The parameter set changeover is carried out in such a way that a continuous control value is maintained even during the changeover. TF4100 65 Version: 2.2.4 Name Type Description tCtrlCycleTime TIME Cycle time with which the control loop is processed. This must be greater than or equal to the TaskCycleTime. The function block uses this input value to calculate internally whether the state and the output values have to be updated in the current cycle. tTaskCycleTime TIME Cycle time with which the function block is called.
If the function block is called in every cycle this corresponds to the task cycle time of the calling task. fKp FLOAT Controller amplification / controller coefficient tTn TIME Integral action time; if this is parameterized to T#0s, the I component is deactivated. tTv TIME Derivative action time; if this is parameterized to T#0s, the D component is deactivated. tTd TIME Damping time fOutMaxLimit FLOAT Upper limit at which integration is halted and to which the output is limited (ARW measure). Reaching this limit is indicated by a TRUE at the bARWActive output. fOutMinLimit FLOAT Lower limit at which integration is halted and to which the output is limited (ARW measure).
Reaching this limit is indicated by a TRUE at the bARWActive output. bPInTheFeedbac kPath BOOL Input value of the internal P-element can be selected with this input (see functional diagram). Standard setting: FALSE bDInTheFeedbac kPath BOOL Input value of the internal D-element can be selected with this input (see functional diagram). Standard setting: FALSE bARWOnIPartOn ly BOOL If this parameter is FALSE (the standard setting), the integration of the I-component is halted if the complete controller output reaches the upper or lower limit. If it is TRUE, the integration is halted if the I- component (the output of the integrator) reaches some limit. (Cf. functional diagram.)