PLC API Additional functions Switching off the I-component in the Outer Window Integration of the control deviation is halted if the control deviation is greater than the fOuterWindow parameter. In this way it is possible to prevent an extremely large I-component from developing if the control deviation is large, since this could lead to a marked overshoot. If it is not wanted, the function can be disabled by setting fOuterWindow:= 0 . Linear reduction of the I-component in the Inner Window With this function it is possible to drive the I-component linearly down to zero in the range specified by the fInnerWindow parameter.
If it is not wanted, the function can be disabled by setting fInnerWindow := 0 . Output dead band If the parameter fDeadBandOutput > 0 is set, the output is set to zero when it is within the range of [ - fDeadBandOutput ... fDeadBandOutput ] . Input dead band If the parameter fDeadBandInput > 0 is set then the output is held constant for as long as the control deviation remains within the range of [ -fDeadBandInput ... fDeadBandInput ] . Step response TF4100 68 Version: 2.2.4