beckhoff TF4100 — 4.2.1.3.11 FB_CTRL_PID_EXT

PLC API ARW VAR_INPUT fSetpointValue : FLOAT; fActualValue : FLOAT; fManSyncValue : FLOAT; bSync : BOOL; eMode : E_CTRL_MODE; bHold : BOOL; END_VAR Inputs VAR_OUTPUT fOut : FLOAT; bMaxLimitReached : BOOL := FALSE; bMinLimitReached : BOOL := FALSE; bARWActive : BOOL := FALSE; fCtrlDerivation : FLOAT; eState : E_CTRL_STATE; bError : BOOL; eErrorId : E_CTRL_ERRORCODES; END_VAR Outputs TF4100 75 Version: 2.2.4 Name Type Description fSetpointValue FLOAT Setpoint of the controlled variable fActualValue FLOAT Actual value of the controlled variable fManSyncValue FLOAT Input with which the PID-element can be set.

bSync BOOL A rising edge at this input sets the PID-element to the value "fManSyncValue". eMode E CTRL MODE _ _ Input that specifies the operation mode [} 173] of the function block. bHold BOOL A TRUE at this input will hold the internal state (and therefore also the output) constant at its current value, independently of the control deviation.