beckhoff TF4100 — 4.2.1.3.12 FB_CTRL_PID_SPLITRANGE

PLC API 4.2.1.3.12 FB_CTRL_PID_SPLITRANGE The function block provides an extended PID transfer element in the functional diagram. This controller enables switching between two parameter sets when control is active. Description This function block is an extension of FB_CTRL_PID , which means that the controller can be used to control systems with two controlled devices for which the transfer behavior are different. A system with one actuator for heating and another actuator for cooling would be a typical application. To optimize the regulation of such TF4100 77 Version: 2.2.4 Name Type Description tCtrlCycleTime TIME Cycle time with which the control loop is processed.

This must be greater than or equal to the TaskCycleTime. The function block uses this input value to calculate internally whether the state and the output values have to be updated in the current cycle. tTaskCycleTime TIME Cycle time with which the function block is called. If the function block is called in every cycle this corresponds to the task cycle time of the calling task. fKp FLOAT Controller amplification / controller coefficient tTn TIME Integral action time; if this is parameterized to T#0s, the I component is deactivated. tTv TIME Derivative action time; if this is parameterized to T#0s, the D component is deactivated.

tTd TIME Damping time fDeadBandInput REAL See description above. fDeadBand Output REAL See description above. fInnerWindow REAL See description above. fOuterWindow REAL See description above. fOutMaxLimit FLOAT Upper limit at which integration is halted and to which the output is limited (ARW measure). Reaching this limit is indicated by a TRUE at the bARWActive output. fOutMinLimit FLOAT Lower limit at which integration is halted and to which the output is limited (ARW measure). Reaching this limit is indicated by a TRUE at the bARWActive output. bPInTheFeed backPath BOOL Input value of the P-element can be selected with this input (see functional diagram).

bDInTheFeed backPath BOOL Input value of the D-element can be selected with this input (see functional diagram). bARWOnIPart Only BOOL If this parameter is FALSE (the standard setting), the integration of the I-component is halted if the complete controller output reaches the upper or lower limit. If it is TRUE, the integration is halted if the I-component (the output of the integrator) reaches some limit. (Cf. functional diagram.)