beckhoff TF4100 — 4.2.1.4.1 FB_CTRL_ACTUAL_VALUE_FILTER

PLC API 4.2.1.4 Filter / ControlledSystemSimulation 4.2.1.4.1 FB_CTRL_ACTUAL_VALUE_FILTER The function block allows a measured input value to be checked for plausibility and filtered. Behavior of the output TF4100 85 Version: 2.2.4 Name Type Description tCtrlCycleTime TIME Cycle time with which the control loop is processed. This must be greater than or equal to the TaskCycleTime. The function block uses this input value for internal calculation to determine whether the state and output values have been updated in the current cycle. tTaskCycleTime TIME Cycle time with which the function block is called.

If the function block is called in every cycle, this corresponds to the task cycle time of the calling task. fKp REAL Controller gain or proportional gain fTn REAL Integral action time: The I component is disabled if this parameter is zero. fTv REAL Derivative action time; the D component is disabled if this parameter is zero.

fTd REAL Damping time fTM REAL Digital valve actuation time in seconds fDeadBandWidth REAL Permissible width of the controller deviation tMinimumPulse Time TIME Minimum pulse time for pulse generator tFilterTime TIME Filter time for actual value filter fWmax REAL Maximum setpoint in °C fWmin REAL Minimum setpoint in °C fYMax REAL Maximum value of the controller output fYMin REAL Minimum value of controller output