PLC API 4.2.1.4.2 FB_CTRL_ARITHMETIC_MEAN n n n c c = е 1 Inputs VAR_INPUT fIn : FLOAT; fManSyncValue : FLOAT; bSync : BOOL; eMode : E_CTRL_MODE; bHold : BOOL; END_VAR Outputs VAR_OUTPUT fOut : FLOAT; eState : E_CTRL_STATE; eErrorId : E_CTRL_ERRORCODES; bError : BOOL; END_VAR TF4100 87 Version: 2.2.4 Name Type Description tCtrlCycleTime TIME Cycle time with which the control loop is processed. This must be greater than or equal to the TaskCycleTime. The function block uses this input value to calculate internally whether the state and the output values have to be updated in the current cycle. tTaskCycleTime TIME Cycle time with which the function block is called.
If the function block is called in every cycle this corresponds to the task cycle time of the calling task. fDeltaMax FLOAT Maximum difference between two input values in sequence. See description above. Name Type Description fIn FLOAT Input value for the mean value filter fManSync Value FLOAT Input value to which the mean value filter can be set, or that is issued at the output in manual mode. bSync BOOL A rising edge at this input sets the mean value filter to the value "fManSyncValue". eMode E CTRL MODE _ _ Input that specifies the operation mode [} 173] of the function block.
bHold BOOL A TRUE at this input will hold the internal state (and therefore also the output) constant at its current value, independently of the input value.