3 Electrical Installation ENGLISH 3 Electrical Installation The figure below shows the main and control circuit wiring. Terminals marked -,+1,+2,B1,B2 are for connecting an option. Do not wire AC power lines to these terminals.

DC reactor (option) For 1-phase power supply use R/L1 and S/L2 Thermal relay Braking resistor (option) Link L1 Fuses R/L1 B1 +1 - +2 B2 U/T1 U Power Supply L2 L3 S/L2 T/L3 J1000 V/T2 W/T3 W V M Main Switch Forward/Stop S1 Shielded Cable Reverse/Stop S2 Ground Option unit connector DIP switch S1 I V Multi-function digital inputs (default setting) MA Multi-function relay output 250 Vac / 30 Vdc (10 mA to 1A) (default setting) Fault +24 V MB MC Shielded ground terminal Analog input power supply +10.5 Vdc, max.

20 mA 2 k Ω +V A1 Analog input 0 to 10 V (20 k Ω ) or 0/4 to 20 mA (250 k Ω ) AM Analog output 0 to +10 Vdc (2mA) (Output frequency) AC AC Monitor output (default setting) Analog input Symbols: Use twisted pair cables Indicates a main circuit terminal Use shielded twisted pair cables Indicates a control circuit terminal. I80E-EN J1000 Quick Start Guide 11 External Fault Fault Reset Multi-speed 1 S3 S4 S5 +24 DIP SINK SC switch S3 SOUR