omron — Wiring Specification

3 Electrical Installation ‹ Wiring Specification „ Main Circuit Use the fuses and line filters listed up in the table below when wiring the main circuit. Make sure not to exceed the given tightening torque values. Tightening Torque Values Tighten the main circuit terminals using the torque values provided by the table below. „ Control Circuit Use wires within the specification listed below. For safe wiring use solid wires or flexible wires with ferrules. The stripping length or ferrule length should be 6 mm. 12 I80E-EN J1000 Quick Start Guide Model JZA† EMC Filter Type Main Fuse (Ferraz) Recom.

Motor cable [mm²] Main Circuit Terminal Sizes Schaffner R/L1,S/L2,T/L3, U/T1, V/T2,W/T3, - , +1, +2 B1, B2 GND B0P1 A1000-FIV1010-SE A6T15 2.5 M3.5 M3.5 M3.5 B0P2 A6T20 2.5 M3.5 M3.5 M3.5 B0P4 A6T20 2.5 M3.5 M3.5 M3.5 B0P7 A1000-FIV1020-SE A6T40 2.5 M4 M4 M4 B1P5 A6T40 4 M4 M4 M4 20P1 A1000-FIV2010-SE A6T10 2.5 M3.5 M3.5 M3.5 20P2 A6T10 2.5 M3.5 M3.5 M3.5 20P4 A6T15 2.5 M3.5 M3.5 M3.5 20P7 A6T20 2.5 M3.5 M3.5 M3.5 21P5 A1000-FIV2020-SE A6T25 2.5 M4 M4 M4 22P2 A6T30 4 M4 M4 M4 24P0 A1000-FIV2030-SE A6T40 6 M4 M4 M4 40P2 A1000-FIV3005-SE A6T10 2.5 M4 M4 M4 40P4 A6T10 2.5 M4 M4 M4 40P7 A6T20 2.5 M4 M4 M4 41P5 A1000-FIV3010-SE A6T25 2.5 M4 M4 M4 42P2 A6T25 2.5 M4 M4 M4 43P0 A6T25 2.5 M4 M4 M4 44P0 A1000-FIV3020-SE A6T30 2.5 M4 M4 M4 Terminal Size M3.5 M4 Tightening Torque [Nm] 0.8 to 1.0 1.2 to 1.5 Terminal Screw Size Tightening Torque N·m Bare Wire Terminal Ferrule-Type Terminal Applicable wire size mm2 Recomm.

mm2 Applicable wire size mm2 Recomm. mm2 MA, MB, MC M3 0.5 to 0.6 0.25 to 1.5 0.75 0.25 to 1.0 0.5 S1-S5, SC, +V, A1, AC, AM M2 0.22 to 0.25 0.25 to 1.0 0.75 0.25 to 0.5 0.5