Configuration 3 rd step : Check and save configuration Save the configuration unter current name or select menu "File - Save As..." to insert a new name. The OPC-Configurator will save the XML based file. After saving the OPC-configurationfile we get the option to activate this configuration to be the configuration for next startup of OPC-Server. After selecting "Yes" this current configuration will be the start-configuration of the opc-server. With next start of OPC-Server this new configuration will be active. If you activated a new OPC-configuration, but the OPC-Server still has old namespace and settings the reason is that the OPC-Server was not stopped and restarted.
6.1.3 Conversion The OPC server offers the feature to online convert process data. The OPC-Server takes care of online-conversion in both communication directions : : Processvalue --> Communication to OPC-Server --> convertion within OPC-Server --> Communication to OPC-Client --> OPC-Client OPC-Client --> Communication to OPC-Server --> convertion within OPC-Server --> Communication to process --> Processvalue Sample : - KL3202 offers process value of temperatures in unit 1/10 Grad Celsius, e.g. 200. - The opc-server is configured with a conversion "Factor 10" which is linked to this plc-variable. - The opc-client gets the process value 20 Grad.
- If opc-client writes a new value 25 Grad celsius to OPC-server, the server will convert this to 250 and writes this value to the PLC. Sample The https://infosys.beckhoff.com/content/1033/tcopcserver/Resources/12162181387/.zip contains a PLC project and an OPC conversion definition. OPC-Server presents a converted variable as Datatyp "VT_R8 / Double" to OPC-client - independend of numerical datatyp in the PLC. 1. Step: Configuration of conversion for TwinCAT OPC Server Start TwinCAT-OPC-Configurator "Start - All Programs - TwinCAT System - TwinCAT OPC - TwinCAT OPC Configurator" TS6120 25 Version: 1.2.0