Configuration With previous TwinCAT versions please refer to section "Manual or specific configurations" on this page. Zero configuration (requires TwinCAT 2.10 on host PC) Details : The OPC-XMLDA configuration file "...\wwwroot\TcOpcXmlDa\TcOpcXmlSvrCfg.xml" contains the list of ADS-devices which are available via OPC-XML-DA interface.
By default this list is pre-configured for one local PLC-runtime system (first PLC runtime-system on ADS-port 801) By default the required symbol-information is linked to C:\TwinCAT\Boot\CurrentPlc_1.tpy encoding="utf-8" standalone="no"?> PLC1 0.0.0.0.0.0 801 2000 20000 7 PLC-Control --> C:\TwinCAT\Boot\CurrentPlc_1.tpy 0 With TwinCAT Version 2.10 Build 1240 the PLC Control allows to download the symbol file name>.TYP to the target TwinCAT machine. The TPY file contains information about all available PLC- variables in the PLC-project. OPC-XML DA CE Server requires this TPY-information.
To download the current symbol information in a TPY file navigate in the PLC-Control to "Project-->Options-- >TwinCAT" and check the option "Download Symbol description" With each download of the PLC-code now also the .TPY file is downloaded as "C: \TwinCAT\Boot\CurrentPlc_1.tpy" containing information about symbols of first run time system. (Second runtime system would be "C:\TwinCAT\Boot\CurrentPlc_2.tpy" etc.) Summary: TS6120 35 Version: 1.2.0