beckhoff TS6120 — 6.2.5.2.1 Group

Configuration Name Enter a name to identify the group. If no name is entered, it is the responsibility of the OPC Server to generate a unique name for you. Update Rate Specifies how often, in milliseconds, the OPC server should provide updates for changing data. Time Bias Specifies the time difference in minutes between the client/server and the actual device. The information allows the client to convert the timestamp received by the server back to the local time of the device. Percent Dead band Specifies the percent change in data required to notify the client of a data change.

Language ID Specifies the language to be used by the server when returning values as text for operations on this group. Active State Specifies the active state of the group. When the group is active, the client will receive data change updates for all active items at the specified update rate. Update Notification TS6120 53 Version: 1.2.0