EL6631/EL6632 LED diagnosis PROFINET RUN/Err LED diagnosis PROFINET Err If there are several different errors, then the error that is located at the top of (or higher in) the table is always displayed. LEDs starting up TS6271 25 Version: 1.2 Color green Color red Meaning off flashing 200 ms Terminal starts flashing 200 ms off No name 1s off, 200 ms on off No IP address on off EL terminal is parameterized Color green Color red Meaning off flashing 500 ms no AR established with any device off 1s off, 200 ms on At least one device has not established an AR 1s off, 200 ms on off At least one device has signalled an error, e.g.
that there is a module difference or that the error bit for an IO-CR is set (Problem Indicator) flashing 200 ms off At least one device is signalling that its status is ‘Stop’ (Provider State Stop) on off All PROFINET devices are in data exchange mode Run PN Run/ Err PN Err Meaning off off off No electrical voltage connected to E-bus. The EL6631 must be exchanged if EtherCAT terminals behind it function. off off red on EL terminal is starting up; after approx. 10 seconds, the LED should go out. If this does not happen, the EL6631 module must be exchanged.