PN Controller Protocol PnIoError - number of PROFINET IO devices that have an error PnIoDiag - number of PROFINET IO devices where a diagnosis is available It is possible to check briefly which device or box has a problem in the protocol under Box States. Presently the following error messages are displayed under the “PnIoState”. TS6271 35 Version:
1.2 Num- ber Text Description Remedial action / reason 0 No error No error No error 1 PROFINETDevice state machine is in boot mode PROFINET Device State Machine is still in the start-up phase Not an error, wait 2 Device not found Device does not reply to the Identify Request Check connection, device connected, was the device called by its correct name? 3 The stationname is not unique The station name is not unique There are two or more devices in the network with the same PROFINET name. A correct identification cannot take place. 4 IP could not set IP address could not be set The PROFINET device has rejected the IP settings for some reason. Check whether the IP settings are correct.
5 IP conflict An IP conflict has occurred in the network A possible cause is that several devices have the same IP address. 6 DCP set was not successful There was no reply or an erroneous reply to a DCP Set Check connection, device connected, was the device called by its correct name? 7 Watchdog error The connection was broken off with a Watchdog error Check the cycle time, check the connection, if necessary increase the Watchdog factor. 8 Datahold error The connection was broken off with a Datahold error Frame Data status was invalid for the length of the DataHoldTimer. Restart the device if necessary. 9 RTC3: Sync signal could not started For IRT only: the Sync signal could not be started.
Is EtherCAT Sync signal correct or has Sync0 started?