beckhoff TS6271 — 5.2 Comparison of nominal and actual configuration

Devices at protocol A maximum of two diagnosis parameters are displayed in the list; others are marked by “…”. If the individual message is clicked, all available diagnosis information is displayed in the window below. Cyclic diagnosis via “PnIoBoxState” and “PnIoBoxDiag” These variables are cyclically exchanged with the process image between the PROFINET driver and the System Manager. Presently the following error messages are displayed under the PnIoBoxState. TS6271 44 Version:

1.2 Num- ber Text Description Remedial action / reason 0 No error No error No error 1 PROFINET Device state machine is in boot mode PROFINET Device State Machine is still in the start-up phase Not an error, wait 2 Device not found Device does not reply to the Identify Request Check connection, device connected, was the device called by its correct name? 3 The stationname is not unique The station name is not unique There are two or more devices in the network with the same PROFINET name. A correct identification cannot take place. 4 IP could not set IP address could not be set. The PROFINET device has rejected the IP settings for some reason. Check whether the IP settings are correct.

5 IP conflict An IP conflict has occurred in the network. A possible cause is that several devices have the same IP address.