beckhoff TS6271 — 7.3 Firmware EL/ES/EM/EPxxxx

Appendix Customers can access the data via the EtherCAT fieldbus and its communication mechanisms. Acyclic mailbox communication or register access to the ESC is used for updating or reading of these data. The TwinCAT System Manager offers mechanisms for programming all 3 parts with new data, if the slave is set up for this purpose. Generally the slave does not check whether the new data are suitable, i.e. it may no longer be able to operate if the data are unsuitable. NOTICE Risk of damage to the device! Firmware downloads to an EtherCAT device must not be interrupted. Flawless EtherCAT communication must be ensured. CRC errors or LostFrames must be avoided.

The power supply must adequately dimensioned. The signal level must meet the specification. Device description ESI file/XML NOTICE Update of the ESI description/EEPROM Some slaves have stored calibration and configuration data from the production in the EEPROM. These are irretrievably overwritten during an update. The ESI device description is stored locally on the slave and loaded on start-up. Each device description has a unique identifier consisting of slave name (9 digits) and a revision number (4 digits). Each slave configured in the System Manager shows its identifier in the EtherCAT tab (device identifier from name EL3204-0000 and revision -0016 ):

The configured identifier must be compatible with the actual device description used as hardware, i.e. the description which the slave has loaded on start-up (in this case EL3204). Normally the configured revision must be the same or lower than that actually present in the terminal network. For further information on this, please refer to the EtherCAT system documentation . Update of XML/ESI description The device revision is closely linked to the firmware and hardware used. Incompatible combinations lead to malfunctions or even final shutdown of the device. Corresponding updates should only be carried out in consultation with Beckhoff support.

Display of ESI slave identifier The simplest way to ascertain compliance of configured and actual device description is to scan the EtherCAT Boxes in TwinCAT mode Config/Freerun. Scan the subordinate field by right-clicking on the EtherCAT device in Config/FreeRun mode: TS6271 73 Version: 1.2