PLC API cbRecordArraySize : UDINT; pDesAddr : DWORD; bExecute : BOOL; tTimeout : TIME := T#15s; END_VAR sNetID : Is a string containing the AMS network identifier of the target device to which the ADS command is directed. hDBID : Is the ID of the database to be used. sProcedureName : Provides the name of the stored procedure. cbParameterList : Provides the size of a parameter list in bytes. pParameterList : Provides the address of a parameter list. nStartIndex : Gives the index of the first data record that is to be read. nRecordCount : Gives the count of data records that are to be read. cbRecordArraySize : Provides the size of an array structure in bytes. pDestAddr :
Provides the address of the array structure into which the data records are to be written. bExecute : The command is executed with the rising edge. tTimeout : States the time before the function is cancelled. VAR_OUTPUT VAR_OUTPUT bBusy : BOOL; bError : BOOL; nErrID : UDINT; sSQLState : ST_DBSQLError; nRecords : UDINT; END_VAR bBusy : The command is in the process of being transmitted by ADS. No new command will be accepted if "bBusy" remains TRUE. bError : Becomes TRUE, as soon as an error occurs. nErrID : Supplies the ADS Error Code [ } 132] or the TcDatabaseSrv_Error_Codes [ } 135] when the bError output is set. sSQLState :
Supplies the SQL error code [ } 89] of the specified database type. nRecords : Returns the number of data records. Requirements TS6420 80 Version: 1.2 Development environment Target system type PLC libraries to be linked TwinCAT v2.10.0 PC or CX (x86) TcDatabase.Lib (from Version 1.0.17) TwinCAT v2.10.0 CX (ARM)