TwinCAT ADS-Device-Documentation TX1000 116 Version: 1.2 Index offset (Hex) Access Controller type Data type Phys. unit Definition range Description Remarks 0x00000207 Read/Write PID (velocity) REAL64 % [0.0...1.0] Maximum out- put limitation (±) for D-part in percent (default setting: 0.1 == 10%) Velocity control 0x0000020D Read/Write P/PID (velocity) REAL64 mm/s [0.0 ... 10000.0] "dead band" for velocity error (control devia- tion) (for P/PID con- trollers with ve- locity or torque interface) Reserved func- tion 0x00000220 Read/Write P/PID (velocity) REAL64 s ≥0 PT-2 filter value for velocity er- ror (vel. control difference) Velocity control, no standard!
0x00000221 Read/Write P/PID (velocity) REAL64 s ≥0 PT-1 filter value for velocity er- ror (vel. control difference) Reserved func- tion, no stan- dard! 0x00000250 Read/Write P/PI (observer) UINT32 1 s. ENUM (≥0) Observer mode [} 136] for con- troller with torque interface 0: OFF (default) 1: LUEN- BERGER From TC 2.10 Build 1320 0x00000251 Read/Write P/PI (observer) REAL64 Nm / A >0.0 Motor: Torque con- stant K T 0x00000252 Read/Write P/PI (observer) REAL64 kg m2 >0.0 Motor: Moment of iner- tia J M 0x00000253 Read/Write P/PI (observer) REAL64 Hz [100.0 ... 2000.0] Default: 500 Bandwidth f 0 0x00000254 Read/Write P/PI (observer) REAL64 1 [0.0 ... 2.0] Default:
1.0 Correction fac- tor k c 0x00000255 Read/Write P/PI (observer) REAL64 s [0.0 ... 0.01] Default: 0.001 Velocity filter (1st order): Time constant T 0x00000A03 Read/Write PID (MW) REAL64 cm^2 [0.0 ...1000000] Cylinder area A of the A side A in cm^2 0x00000A04 Read/Write PID (MW) REAL64 cm^2 [0.0 ...1000000] Cylinder area A of the B side B in cm^2 0x00000A05 Read/Write PID (MW) REAL64 cm^3/s [0.0 ...1000000] Nominal vol- ume flow Q nom in cm^3/s 0x00000A06 Read/Write PID (MW) REAL64 bar [0.0 ...1000000] Rated pressure or valve pres- sure drop, P nom in bar 0x00000A07 Read/Write PID (MW) UINT32 1 [1 ... 255] Axis ID for the system pres- sure P o