beckhoff TS6250 — 7.1.6 FB_MBWriteSingleReg (Modbus function 6)

PLC libraries Requirements 7.1.6 FB_MBWriteSingleReg (Modbus function 6) This function is used for writing an individual output register. 16 bit access is used. VAR_INPUT VAR_INPUT sIPAddr : STRING(15); nTCPPort : UINT:= MODBUS_TCP_PORT; nUnitID : BYTE:=16#FF; nMBAddr : WORD; nValue : WORD; bExecute : BOOL; tTimeout : TIME; END_VAR sIPAddr : Is a string containing the IP address of the target device. nTCPPort : Port number of the target device. nUnitID : Identification number of a serial sub-network device. If a device is addressed directly via TCP/IP, this value must be 16#FF. nMBAddr : Address of the output register (word offset). nValue :

Value to be written into the register (word value). bExecute : The function block is activated by a rising edge at this input. tTimeout : States the length of the timeout that may not be exceeded by execution of the ADS command. VAR_OUTPUT VAR_OUTPUT bBUSY : BOOL; bError : BOOL; nErrId : UDINT; END_VAR bBusy : When the function block is activated this output is set. It remains set until an acknowledgement is received. bError : If an ADS error should occur during the transfer of the command, then this output is set once the bBusy output is reset. nErrId : Supplies the ADS error number when the bError output is set. TS6250 28 Version:

1.2 Development environment Target system type PLC libraries to be linked TwinCAT v2.8.0 PC (i386) TcModbusSrv.Lib Function specific ADS error code Possible reason 0x8001 Modbus function not implemented