PLC libraries nTCPPort: Port number of the target device. nUnitID: Identification number of a serial sub-network device. If a device is addressed directly via TCP/IP, this value must be 16#FF. nQuantity: Number of output registers (data words) to be written. nMBAddr: Start address of the output registers to be written (word offset). cbLength: Contains the max. byte size of the source buffer. The minimum buffer byte size must be: nQuantity * 2 . pSrcAddr: Contains the address of the source buffer containing the data to be written. The buffer can be a single variable, an array or a structure, whose address can be found with the ADR operator.
bExecute The function block is activated by a rising edge at this input. tTimeout: States the length of the timeout that may not be exceeded by execution of the ADS command. VAR_OUTPUT VAR_OUTPUT bBUSY : BOOL; bError : BOOL; nErrId : UDINT; END_VAR bBusy: When the function block is activated this output is set. It remains set until an acknowledgement is received. bError: If an ADS error should occur during the transfer of the command, then this output is set once the bBusy output is reset. nErrId: Supplies the ADS error number when the bError output is set. Example of calling the block in FBD: PROGRAM Test VAR fbWriteRegs : FB_MBWriteRegs; bWriteRegs : BOOL; bWriteRegsBusy :
BOOL; bWriteRegsError : BOOL; nWriteRegsErrorId : UDINT; nWriteRegsCount : UDINT; nQuantity : WORD := 3; nMBAddr : WORD := 4; arrData : ARRAY [1..3] OF WORD; END_VAR TS6250 32 Version: 1.2 Function specific ADS error code Possible reason 0x8001 Modbus function not implemented 0x8002 Invalid address or length 0x8003 Invalid parameters: - wrong number of registers 0x8004 Modbus server error