beckhoff TS6250 — 7.1.9 FB_MBReadWriteRegs (Modbus function 23)

PLC libraries nTCPPort : Port number of the target device. nUnitID : Identification number of a serial sub-network device. If a device is addressed directly via TCP/IP, this value must be 16#FF. nReadQuantity : Number of output registers (data words) to be read. The value of nReadQuantity must be > 0. nMBReadAddr : Start address of the output registers to be read (word offset). nWriteQuantity : Number of output registers (data words) to be written. The value of nWriteQuantity must be > 0. nMBWriteAddr : Start address of the output registers to be written (word offset). cbDestLength : Contains the max. byte size of the destination buffer.

The minimum destination buffer byte size must be nReadQuantity * 2 . pDestAddr : Contains the address of the destination buffer into which the data are to be read. The buffer can be a single variable, an array or a structure, whose address can be found with the ADR operator. cbSrcLength : Contains the max. byte size of the source buffer. The minimum source buffer byte size must be nWriteQuantity * 2 . pSrcAddr : Contains the address of the source buffer containing the data to be written. The buffer can be a single variable, an array or a structure, whose address can be found with the ADR operator. bExecute : The function block is activated by a rising edge at this input. tTimeout :

States the length of the timeout that may not be exceeded by execution of the ADS command. VAR_OUTPUT VAR_OUTPUT bBUSY : BOOL; bError : BOOL; nErrId : UDINT; cbRead : UDINT; END_VAR bBusy : When the function block is activated this output is set. It remains set until an acknowledgement is received. bError : If an ADS error should occur during the transfer of the command, then this output is set once the bBusy output is reset. nErrId : Supplies the ADS error number when the bError output is set. cbRead: Contains the number of bytes currently read. Example of calling the block in FBD: PROGRAM Test VAR fbReadWriteRegs : FB_MBReadWriteRegs; bReadWriteRegs : BOOL; bReadWriteRegsBusy :

BOOL; bReadWriteRegsError : BOOL; nReadWriteRegsErrorId : UDINT; nReadWriteRegsCount : UDINT; nRdQuantity : WORD; nRdMBAddr : WORD; TS6250 34 Version: 1.2 Function specific ADS error code Possible reason 0x8001 Modbus function not implemented 0x8002 Invalid address or length 0x8003 Invalid parameters: - wrong number of registers 0x8004 Modbus server error