beckhoff TS6250 — 7.1.11.10 FB_MBUdpDiagnose (Modbus function 8)

PLC libraries 7.1.11.10 FB_MBUdpDiagnose (Modbus function 8) The diagnosis function provides a series of tests for checking the communication system between the master and the slave and for examining a variety of internal error states within the slave. VAR_INPUT VAR_INPUT sIPAddr : STRING(15); nTCPPort : UINT:= MODBUS_TCP_PORT; nUnitID : BYTE:=16#FF; nSubFnc : WORD; nWriteData : WORD; bExecute : BOOL; tTimeout : TIME; END_VAR sIPAddr : Is a string containing the IP address of the target device. nTCPPort : Port number of the target device. nUnitID : Identification number of a serial sub-network device. If a device is addressed directly via TCP/IP, this value must be 16#FF. nSubFnc :

The sub-function to be executed. nWriteData : The data word to be written. bExecute : The function block is activated by a rising edge at this input. tTimeout : States the length of the timeout that may not be exceeded by execution of the ADS command. VAR_OUTPUT VAR_OUTPUT bBusy : BOOL; bError : BOOL; nErrId : UDINT; nReadData : WORD; END_VAR bBusy : When the function block is activated this output is set. It remains set until an acknowledgement is received. bError : If an ADS error should occur during the transfer of the command, then this output is set once the bBusy output is reset. nErrId : Supplies the ADS error number when the bError output is set. nReadData:

Supplies the read data word. TS6250 49 Version: 1.2 Function specific ADS error code Possible reason 0x8001 Modbus function not implemented 0x8002 Invalid address or length 0x8003 Invalid parameters: