Samples M0 AT%MB0 : ARRAY [0..3] OF WORD; nValue : ARRAY [0..3] OF WORD :=0,10,100,1000; fbWriteRegs : FB_MBWriteRegs; bWriteRegs :
BOOL; END_VAR IF NOT bWriteRegs THEN nValue[0]:= nValue[0]+1; nValue[1]:= nValue[1]+1; nValue[2]:= nValue[2]+1; nValue[3]:= nValue[3]+1; bWriteRegs :=TRUE; fbWriteRegs.sIPAddr :=ipAddr; fbWriteRegs.nQuantity := 4; fbWriteRegs.nMBAddr := 16#3000; fbWriteRegs.cbLength := SIZEOF(nValue); fbWriteRegs.pSrcAddr := ADR(nValue); fbWriteRegs.tTimeout := T#5s; fbWriteRegs(bExecute:=TRUE); ELSE IF NOT fbWriteRegs.bBUSY THEN bWriteRegs :=FALSE; END_IF fbWriteRegs(bExecute:=FALSE); END_IF The array arrValue will be written to the memory area of the plc (M0) by a rising edge on bWriteRegs.
https://infosys.beckhoff.com/content/1033/tcmodbussrv/Resources/11379456139/.zip Also see about this 2 Mapping between Modbus and ADS [ } 14] TS6250 52 Version: 1.2