Visualization Example for a command line: C:\TwinCAT\Plc\TCatPlcCtrlHmi.exe D:\PROJECTS\PROJECT.PRO /visu v_firstvisupage The project project.pro will start with the visualization POU 'v_firstvisupage'. If the visualization should be started automatically with TwinCAT PLC Control, this can be done with a connection in TwinCAT StartUp (All Users) to the 'TCatPlcCtrlHmi.exe' and the named parameters. Paths containing spaces must be bordered by quotation marks ("). Operating: The project will start in full screen mode with the entrance POU. TwinCAT PLC HMI can be operated corresponding to the functions of the visualization elements via keyboard and mouse.
If there is no visualization element configured with a corresponding function, TwinCAT PLC HMI at any time can be terminated by pressing . 9.7 Target Visualization The Target-Visualization is one of the possible ways to use a TwinCAT Visualization. TwinCAT PLC Control can create ST code (Structured Text) for the visualization objects of a project. This code can be downloaded to the PLC together with the normal project code. Thus, if it is supported by the target system and if an appropriate monitor is available, the visualization can be started directly on the PLC computer. It is not necessary any longer that the programming system is running in order to run the visualization.
This means a considerable reduction of storage use. Functions of the library SysLibTargetVisu.lib offer information about mouse-clicks performed by the user resp. entries of the dynamic textlist [ } 259] and allow to use these information in the program. 9.7.1 Feature overview of visualisation with TwinCAT It is shown in this table which possibilities the visualisation offers with TwinCAT. TwinCAT 2 PLC Control 252 Version: 1.0