Linking into a PLC Program PROGRAM MAIN VAR ComControl: KL6ControlBC; Timer: TON; Receive: ReceiveByte; Send: SendByte; Rb: BYTE; Sb: BYTE; END_VAR ComControl( CoMin:=KL6InData, CoMout:=KL6OutData, TxBuffer:=TxBuffer, RxBuffer:=RxBuffer ); Timer(IN:=TRUE,PT:=T#1S ); IF Timer.Q THEN IF Sb=0 THEN Sb:=64; END IF Sb:=Sb+1; IF Sb>90 THEN Sb:=64; END IF Send(SendByte:=Sb, TxBuffer:=TxBuffer); Timer(IN:=FALSE); END IF 7.5 Sending and Receiving Sending data In the example program included, data is sent via the serial interface at one-second intervals, and the program reacts immediately to an arriving character.
Possible errors More than one character may be transmitted during one PLC cycle, provided they can be accepted by the send buffer. If the send buffer overflows, the busy output of the send block will remain TRUE after it has been called. In that case the last character is not sent, and the block must be called again with the same input data in the next PLC cycle. How full a buffer is can be determined at any time (e.g. TxBuffer.Count or TxBuffer.FreeByte). PROGRAM MAIN VAR ComControl: KL6ControlBC; Timer: TON; Receive: ReceiveByte; Send: SendByte; Rb: BYTE; Sb:
BYTE; END_VAR ComControl( CoMin:=KL6InData, CoMout:=KL6OutData, TxBuffer:=TxBuffer, RxBuffer:=RxBuffer ); Timer(IN:=TRUE,PT:=T#1S ); IF Timer.Q THEN IF Sb=0 THEN Sb:=64; END IF Sb:=Sb+1; IF Sb>90 THEN Sb:=64; END IF TX1200 19 Version: 1.1