Overview 2 Overview | Overview The TwinCAT System Manager is the central configuration tool of the TwinCAT System. It is where the inputs and outputs of the software tasks and the physical inputs and outputs of the connected fieldbusses are managed. The individual software tasks (e.g. PLC tasks) each operate on their own private process image so that the addresses of the symbols mapped in the process image (variables) are relevant and valid only within that particular task. The I/O information of the individual Software Tasks is read from and entered in the TwinCAT System Manager. From there, the installed fieldbusses and their connected modules/boxes are also described.
The logical and physical inputs and outputs are assigned to one another by linking software task variables and fieldbus variables. Task-task communication: With the aid of the TwinCAT System Manager, the ”in and outputs” of a task can be cyclically exchanged with the ”out and inputs” of another task. The data consistency remains thereby intact. Variable orientated: The smallest addressable and linkable unit is a variable. Variables can be individual bits, bytes, 16 bit data words, 32 bit data words etc. Variables can also be structures or arrays (fields) consisting of other data types. Process Images: Variables are always precisely assigned to a process image, i.e.
the address of the variable is indicated unambiguously in its process image - but only within that process image. Each software task and each fieldbus possesses precisely one process image (exception: PLC run time system tasks share a combined process image). Assignments: The TwinCAT System Manager produces individual assignments which contain the links created. Assignments are produced between software tasks and fieldbus devices and between software tasks if these have mutually linked variables. I.e. if a PLC task variable is linked to the variables of a fieldbus an assignment will be produced between these two.
If the same PLC task has other variables linked with another fieldbus, a second assignment will be generated. The assignments contain the corresponding copying directives to enable the exchange of the corresponding variables at the run time. Fieldbus independence : When defining and programming the software tasks participating in the TwinCAT system it is not necessary to know the type and structure of these or the fieldbus used. Programming is carried out with the aid of logical variables which are defined locally within the software itself.
The TwinCAT System Manager links these logical variables with other variables, which correspond either to physical inputs and outputs on the fieldbus or to logical variables of other tasks. The type and the special properties of each fieldbus do not need to be known or considered. TwinCAT System Manager supports all standard commercial fieldbuses and some other PC standard interfaces: Beckhoff Lightbus Profibus DP, MC (DP-V2) Interbus CANopen SERCOS DeviceNet Ethernet EtherCAT Beckhoff Real-Time Ethernet TwinCAT 2 10 Version: 1.7