Bus Terminal Controller | Data Exchange PC/Bus Terminal Controller Cancel Closes the dialogue without adding a terminal to the configuration. You can find further information about the configuration of the terminals in the System Manager under: Terminal-specific Dialogues [ } 107] . 9.3 Data Exchange PC/Bus Terminal Controller | Data Exchange PC/Bus Terminal Controller For Bus Terminal controllers you can define below PLC variables data exchange variables (see example in the tree view below) for the fieldbus-based PC to PC communication. If you select a BC in the tree view of the TwinCAT System Manager, the following BC Mini PLC dialogue (amongst others) will appear on the right-hand side:
”PLC” Dialogue PLC Cycle Time The reserved Mini PLC cycle time. During this period, no data will be sent by the BC to the fieldbus. Background Time Time for the processing of the communication via the fieldbus (includes program download, debugging,..). PLC Var. Offs IN Start offset of the data exchange variables in the input area of the BC Process Image [ } 113] . PLC Var. Offs OUT Start offset of the data exchange variables in the output area of the BC Process Image [ } 113] . AMS Response during download Can be disabled for compatibility reasons in old Bus Terminal controllers (BC3100 and BC2000).
Newer bus controller firmware versions acknowledge the receipt of individual download sequences. This checkbox must therefore be activated (in all cases for BC9000). Start with Configuration Error Even if the configured BC9000 is not connected to the network, it is possible to start the TwinCAT system if this checkbox is enabled. Retain Data Store Retain Data : Activates the support of residual data in the Bus Terminal controller. Size : Size of the retain data area within the Bus Terminal controller (%M x 0 .. %Mxy). TwinCAT 2 112 Version: 1.7