beckhoff — 9.6 Merging the BC3100 in the TwinCAT System Manager

Bus Terminal Controller | Merging the BC3100 in the TwinCAT System Manager PLC Variables PLC variables are variables that are situated in the BC3100 from addresses %IB128 and %QB128. This offset can be shifted. These addresses are not assigned to any terminal, so that signals or data can be transmitted to or received from the master via the PLC variables. Remanent Variables Retained or remanent variables are data that retain their value when voltage is not present. In PLC Control this data is placed in the allocated flags area. Following the default setting, this means that all the variables from %MB0 - %MB63 are RETAIN data.

The maximum setting is 512 bytes Terminal Bus (K-Bus) Update Double Cycle: Terminal bus inputs before the PLC cycleTerminal bus outputs after the PLC cycle Before PLC: Terminal bus inputs and outputs before the PLC cycle After PLC: Terminal bus inputs and outputs after the PLC cycle Program download via the fibre optic ring TwinCAT offers a facility for transferring the program to the BC3100 over the optical fibre ring. To do this, string communication and the Ams/Ads must be activated in the system manager under the ADS/AMS tab. The TwinCAT system is started after the configuration has been saved. Now the BC3100 target system can be selected in PLC Control. TwinCAT 2 121 Version: 1.7