beckhoff — 10.1 Mapping Types and Graphical Display

Mappings | Mapping Types and Graphical Display Map Type Synchronous : A process image is master, second slave. The master actuates the outputs for writing (e.g. to fieldbus card C1220, ..) and checks that the other side has completed its I/O cycle in order to read the current inputs. The other side has no independent cycle time in this case (Engl. timekeeper). Asynchronous Is set, e.g. in the event of links from two tasks, or with devices operating on their own cycle times (e.g. COM port) and independently regulates and thereby the refreshes inputs and outputs.

The exchange of information between two Process Images [ } 46] thereby takes place in the case of asynchronous mapping based on the three-buffer principle. For some device types (e.g. the multitasking Profibus card FC310x ) a mix of synchronous and asynchronous assignment (mappings) is used. In relation to the device the higher Priority [ } 62] task behaves in a synchronous manner while the lower priority task is asynchronous. Watchdog In the case of asynchronous mapping ( seeMap Type ) a task could fail to conclude correctly (endless loop), the other task is, however, processed as normal and therefore continues to read old values from the buffers.

A maximum lifecycle value is specified to prevent this occurring. Once the value is reached, all buffer values are reset to ‘0’. Timing Activates the timing of a synchronous assignment ( see Map Type ). Process Image A Shows the task name assigned to process image A. Process image B Shows the task name assigned to process image B. Show A -> B and/or B -> A Exchanges the direction of both process images in the displayed view. The colors green and pink represent process images A and B. The colors yellow and blue are in/outputs of the process image. Click with the mouse on the in/outputs to display a tool tip with the variable terminal names. TwinCAT 2 128 Version: 1.7