Reference | I/O Devices "CIF x0 DPM / PB" tab Address : Enter the DPRAM card address here. This address is jumped on the card and can assume the following values: from 0xC8000 to 0xEF800 in steps of 0x800 (and 0x2000 at CIF 30-PB) Search : Searches the computer for available CIF-30 cards (only when TwinCAT is active) Stations No .: Each Profibus device requires a unique station number - including the master. Baudrate : Set the Profibus baudrate. Automatically tests whether the connected slave also supports this baudrate. Cycle Ticks : The smallest possible cycle time for the currently specified slave is set here. It can be manually increased (in ms) Synchronous Mode :
The highest priority task linked with the corresponding device controls the fieldbus cycle and is thereby synchronized with the fieldbus. All other tasks are served asynchronously via corresponding buffers. ”Profibus” tab See " Siemens CP5412A2 [ } 141] " Tab ”(Online) DPRAM” See ” Online Display of DPRAM [ } 267] 11.2.2.2 Siemens CP5412 A2 | Siemens CP5412 A2 The DPRAM of the CP5412A2 is 16 or 64 Kbytes. There are no interrupts used. There are no functional differences between the 16k and 64k settings. In general therefore the 16k setting is recommended. Context menu TwinCAT 2 141 Version: 1.7