Reference | I/O Devices ”Profibus” tab The parameters set here are described in the PROFIBUS standard (DIN 19245 part 3 - PROFIBUS-DP), Chapter 7 and should only be changed by expert users. Tab ”(Online) DPRAM” See ” Online Display of DPRAM [ } 267] Input Diagnosis The Siemens CP5412A2 automatically provides two input bytes, which describe the status of the card and the Profibus: DeviceState : General status, which only assumes values 0=OK and 1=error DeviceDpState : DeviceDpState is a flag byte, the individual bits have the following definitions:
0x00 = No error 0x01 = Transmitter fault 0x02 = Master address fault 0x04 = HSA fault 0x08 = Baud rate fault 0x80 = Temp fault TwinCAT 2 144 Version: 1.7