beckhoff — 11.2.3.3 Phoenix IBS SC/I-T and IBS SC/RI/RT-LK

Reference | I/O Devices System StartUp with Incomplete Configuration System StartUp with Incomplete Configuration If you wish the system to start with incomplete configuration you have several options: 1. Alternative Definition : If the potentially unavailable devices are assigned an alternative, they will be disabled when the system is started (this can only take place if deliberately activated using Control_Active_Configuration (see. " InterBus-S [ } 318] ” tab for that device)). 2. Special Device Settings : A Control_Active_Configuration command can be defined for individual devices. This will be executed before activating the configuration (see "InterBus-S Tab” for that device).

Note that a Control_Active_Configuration command will affect subsidiary devices! 3. Special configuration during system StartUp by the PLC : You can tell the card to switch on in PAR_READY mode at the system StartUp and have further configuration and bus control carried out by the PLC. In this case proceed as follows: 4. Deselect automatic " Active_Configuration [ } 150] ". This will leave the card in PAR_READY state 5. After the system start, you can individually deselect those devices which you do not require or use a Group Definition [ } 318] (Control_Active_Configuration), so that only remaining (present) devices are activated.

De-selection (switching off selected devices) is generally carried out from the PLC via ADS. You can link in the PLC library "PlcIbsScit.lib" to view the necessary ADS commands in the form of options. 6. Actuate "Active_Configuration" via ADS 7. Actuate "Start_Data_Transfer" via ADS If you later wish to reactivate the inactive devices, use also "Control_Active_Configuration" via ADS when the system is in RUN mode. ISA IBS SC/RI/RT-LK Slave Interface (System Coupler) The slave interface is configured by the higher level INTERBUS system. The process data length of the slave interface can be configured and has a maximum length of 10 words.

When the IBS SC/RI/RT-LK is added to the I/O configuration, the process data length of the system coupler is set to 10 words, and the parameter channel data length to 0 bits (no PCP). The INTERBUS interfaces of the IBS SC/RI/RT-LK are translated by a medium converter from copper to optical fibre transmission. The medium converter has ID code 0x08 and length code 0x0. It is added automatically by the System Manager to the card's I/O configuration. Do not initiate operation of the higher level INTERBUS system until the system coupler has the final configuration, since configuration changes will put the higher level system into an error state. TwinCAT 2 155 Version: 1.7