Reference | I/O Devices ID code 3: no PCP, maximum process data length 10 words. ID code 235: parameter channel length 1 word, maximum process data length 9 words. ID code 232: parameter channel length 2 words, maximum process data length 8 words. ID code 233: parameter channel length 4 words, maximum process data length 6 words. The system coupler can be supplied with an external voltage so that data can still continue to be exchanged in the higher-level system even if the lower level master fails. The slave's configuration cannot be permanently saved on the IBS SC/RI/RT-LK card and is reset to default values whenever the PC boots again.
The card's configuration memory is cleared, and the higher-level system reports a peripheral error. In the default configuration, the system coupler has ID code 233 and length code 0x4 (4 words). The parameter channel is 64 bits long. Configuration of the IBS SC/RI/RT-LK Slave Interfaces in the Higher-level INTERBUS System The system coupler in the higher-level system is preceded by a bus terminal with ID code 0x0C and length code 0x0. The system coupler's ID code and length code are specified by the configuration of the system coupler in the lower-level system. 11.2.3.4 Hilscher CIF50-IBS | Hilscher CIF50-IBS 11.2.3.4.1 Hilscher CIF50-IBS | Hilscher CIF50-IBS System requirements:
TwinCAT 2.9 build > 1000 and higher. The CIF50-IBS is an Interbus-S slave PCI card with 8 kB DPRAM. Supported baud rates: 500kBit and 2MBit. The baud rate can be configured via a DIP switch on the card. The new baud rate will only apply after a system restart (power OFF). The slave card is offered in two versions, i.e. with copper or optical fibre fieldbus interface. TwinCAT configuration is identical in both cases. "General" tab See "General" tab [ } 132] TwinCAT 2 157 Version: 1.7