beckhoff — 11.2.3.4.2 CIF50-IBS error codes

Reference | I/O Devices TwinCAT 2 167 Version: 1.7 Error number Description 110 Watchdog Failure A watchdog failure has occurred. Additional Code: Data exchange mode 111 No Data Acknowledge The user has failed to acknowledge the data cycle (in data exchange mode 0). Additional Code: Data exchange mode 112 Bus Not Active The InterBus is NOT ACTIVE state. Additional Code: 0 (not used) _ 113 Bus Reset The InterBus is in RESET state. Additional Code: 0 (not used) 114 Application An application (USER) error has been detected by the ALI task. Additional Code: One of the error numbers marked with *.

115 * No Bus Communication The state of the VFD object is not 'Ready for Communication', or the communication state of the InterBus is not 'Active' (i.g., the board is not connected). 116 Negative Read.Confirmation Received A negative Read.Confirmation has been received from a communication partner. Additional Code: CR of deficient confirmation 117 Negative Write.Confirmation Received A negative Write.Confirmation has been received from a communi-cation partner. Additional Code: CR of deficient confirmation 118 * Object Non Existent The task could not find the requested object. 119 * Client Not Ready The state of the PCP client is NOT READY; a request is still active.

_ 119 Client Not Ready The state of the PCP client is NOT READY; a request is still active. Additional Code: CR of _ active request 120 Negative Initiate.Confirmation Received A negative Initiate.Confirmation is received. Additional Code: CR of deficient confirmation 121 * Invalid Communication Reference The task could not find the requested communication reference. 122 * Request Still Active A request is queued internally; the request is still active. 123 * Communication Reference Not Open The requested communication reference is not open. 124 Nothing to Process There is no request to process. Additional Code:

CR of deficient confirmation 125 Object Attribute Inconsistent The task has detected an invalid object index for a Read / Write Request or an invalid data length. Additional Code: Object index of the deficient request 126 Type Conflict The task has detected an invalid data type for BOOLEAN, respectively for VISIBLE STRING _ within a Write Indication. Additional Code: Object index of the deficient request 127 Invalid PDU Size The task has detected an invalid PDU size for a Read Request. Additional Code: Object index of the deficient request