Reference | I/O Devices Master In master synchronization mode the card generates its time basis locally. The SYNC is generated with long time quartz accuracy. The start of the TwinCAT task is triggered by the card, delayed by the Shift Time. In this mode the shift time value should be as large as possible. The function "Calculate Equi-Times" helps to configure the optimal shift time. It is started by selecting the corresponding button. Cycle Time: Displays the cycle time of the corresponding highest priority task. The value is updated when the TwinCAT mapping is generated. Sync-Cycle Multiplier: CANopen SYNC Cycle Time = (Task) Cycle Time x Sync-Cycle Multiplier.
Event driven PDO communications and cyclic synchronized PDO communication are frequently combined when used in conjunction with CANopen. To be able to respond rapidly to an event, the TwinCAT task cycle time has to be less than the CANopen SYNC cycle time. Sync-Cycle time Shows the cycle time of the CANopen SYNC telegram. This cycle time is derived from the highest priority task which has process data linked to the card, and the Sync Cycle Multiplier. TwinCAT 2 172 Version: 1.7